车间变电所设备维护规程
一.高压柜
本车间变电所共有板有37面高压柜,型号均为KYN28-12 型。电源从总降压变电所引入,负责给出6台变压器, 18台高压电机及空压站不住3台变压器,4台扎钢工程施工电源,供10KV电源:
37面高压柜名称如下:
KYN28A-12-102 1#电源进线柜
KYN28A-12-103 1#PT柜
KYN28A-12-104 1#高炉1#变压器柜
KYN28A-12-105 2#高炉1#变压器柜
KYN28A-12-106 联合1#变压器柜
KYN28A-12-107 空压站1#变压器柜
KYN28A-12-109 喷煤磨煤机柜
KYN28A-12-110 1#高炉料仓除尘风机柜
KYN28A-12- 111 炉前除尘风机柜
KYN28A-12-112 联合泵房1#常压水泵电机柜
KYN28A-12-113 联合泵房3#常压水泵电机柜
KYN28A-12-114 联合泵房5#常压水泵电机柜
KYN28A-12-115 联合泵房1#高压水泵电机柜
KYN28A-12-116 联合泵房3#高压水泵电机柜
KYN28A-12-117 热风系统1#助燃风机柜
KYN28A-12- 施工电源
KYN28A-12- 备用
KYN28A-12-101 分段柜
KYN28A-12-201 隔离柜
KYN28A-12-202 2#电源进线柜
KYN28A-12-203 2#PT柜
KYN28A-12-204 1#高炉2#变压器柜
KYN28A-12-205 2#高炉2#变压器柜
KYN28A-12-206 联合泵房2#变压器柜
KYN28A-12-207 空压站2#变压器柜
KYN28A-12-208 空压站3#变压器柜
KYN28A-12-210 喷煤排粉风机机柜
KYN28A-12-211 2#高炉料仓除尘风机柜
KYN28A-12-212 联合泵房2#常压水泵电机柜
KYN28A-12-213 联合泵房4#常压水泵电机柜
KYN28A-12-214 联合泵房6#常压水泵电机柜
KYN28A-12-215 联合泵房2#高压水泵电机柜
KYN28A-12-216 联合泵房4#高压水泵电机柜
KYN28A-12-217 热风系统2#助燃风机柜
KYN28A-12-218 热风系统3#助燃风机柜
KYN28A-12- 施工电源
KYN28A-12- 备用
KYN28A-12- 开关柜
K→表示金属铠装式
Y→表示移动式(手车式)
N→户内用
28A→设计序号
12→额定电压12KV
二.变压器主要技术参数
2。1 油浸变压器
额定电压:10500V±5% 冷却方式:0NAN
一次侧额定电压:400V
二次侧额定电流:2309A
一次侧额定电流:87。98A
额定容量:1600KVA
短路阻抗:4。467
连接方式:DYN11
2。2 干式变压器
一次侧额定电压:10KV 冷却方式:AN/AF
二次侧额定电压:400V 温升限值:100K
一次侧额定电流:88A
二次侧额定电流:2309A 连接组别:DYN11
阻抗电压:6。21%
三.维护检查(变压器)
项目 检查内容
总体 电压,电流是否正常,报警,有无异常响声
有无刀开关放电现象
紧固件 瓷瓶有无灼伤放电痕迹
螺丝有无松动,发热,放电现象
冷却系统 油枕油位,温度表,干燥剂颜色
变压器本体温度,风扇是否正常转动
外表 有无异常现象,发热。母排有无发热
四.操作
1. 整个柜子由固定的壳体和装有滚轮的可移开(手动)两部分组成,外壳用钢板分隔成小车室,母线室,电缆接地室和继电仪表室四个部分。本所手车包含断路器手车,电压互感器手车。手车的后门配有连锁机构,断开断路器,打开连锁杆方能打开后门。装后门时,先装上半门,后装下半门。手车可以放置于工作和实验两个位置,柜体上配有限位开关,即实验开关和合闸位置。这两个位置都可合闸,小车也配有连锁,分闸后方可进行小车进出。打开地刀门时,必须先将接地刀合上,合办地刀时先将断路分闸后接至实验位置。
2. 变压器
本变电所给本厂6台变压器供电,其中四台在3#,4#主控室低配,另2台在联合泵房。
主控低配(干式)变压器SCB10-1600/10
联合泵房变压器(油濅变压器)S9-1600/10。5
3. 直流屏及信号系统
直流系统采用2路交流进线,通过可控硅整流成1路直流母线,母线向蓄电池充电,用以控制回路,信号回路,继保和自动装置回路,提供操作电源。它受交流电影响,当电力系统发生故障时能可靠工作。
本文关键字:变电所 操作规程,机械设备 - 操作规程